Moving the Converter Under the Chip: An I²R Loss Audit

The Semiconductor Hub
by
0
Share Facebook X LinkedIn WhatsApp Email
Cutaway view of a processor package with a power converter module mounted directly beneath it and current flowing upward into the chip.

Move the voltage regulator from beside a processor to underneath it, and the resistive loss in the final stretch of copper can fall sharply. In the illustrative 1,000 A model in this post, I²R loss drops from 70 W to 10 W, a cut of about 86%.

The total loss from the 48 V bus to the load falls by much less, from about 161 W to about 114 W, or about 29%, because a converter squeezed under the chip usually gives back some efficiency. That gap between the copper saving and the system saving is the subject of this post, with a calculation you can redo using your own numbers.

Key takeaways

  • I²R loss depends on the square of current, so the place to convert from 48 V to under 1 V sets how far the high current has to travel.
  • Vertical delivery moves loss more than it removes it. In our model, conversion accounts for about 91% of the vertical design's loss.
  • Under our assumptions, the two approaches tie at about 300 A. By 2,000 A, vertical saves nearly half the loss.
  • The figure to demand from a vertical module is its efficiency at your current and your voltage. Peak efficiency can sit far from the full-load number.

What moves, and what does not

Vertical power delivery and backside power are easy to confuse because both describe power arriving from below. They work at different scales. Backside power delivery rearranges metal inside the die, and the fight there is over on-die IR drop and routing tracks. Vertical power delivery moves the converter, which sits on a board or in a package, closer to the point of load.

In a lateral layout, the final regulator sits on the board next to the package, so high current at under 1 V crosses board copper, package layers and bumps. In a vertical layout, 48 V or an intermediate voltage is carried to a spot beneath the die, and the high current has only a short path upward. Published work places that converter at several heights:

Converter locationExample in the literatureWhat it asks of the design
Underside of the motherboardUC Berkeley's APEC 2024 converter is intended for this position, feeding the processor through board viasBoard via planning and cooling on the bottom side
Inside the package substrateUniversity of Illinois Chicago's 2026 framework embeds GaN switches and arrays of small passivesEmbedded passives, plus a share of the area under the die
On or within an interposerThe same group's 2023 architecturesCompact high-ratio converters and integrated passives
Dedicated power dieThe 2023 two-stage architectures, for the lower-voltage stageA further die in the stack, plus heat at that level

The closer the converter gets, the smaller and hotter it has to be. Our post on silicon interposers gives useful background on the structures involved at the interposer level.

The idea in plain words

A large AI processor runs at well under 1 V but draws hundreds or thousands of amps. Power reaches the rack at 48 V, so somewhere a converter has to step it down, and after that point the current is huge. Copper wastes power as heat in proportion to the square of the current (I²R), so every millimeter that the high current travels costs energy.

The usual layout puts the final converter on the board beside the processor package. Vertical power delivery puts it underneath, so the high current only has a short hop up into the chip. That cuts the copper loss sharply.

The catch is the converter itself. A converter squeezed into the small space under a chip usually runs a little less efficiently and gets hotter, and the energy it wastes can eat much of what the shorter copper path saved. So the honest question is not "how much copper loss goes away?" but "what is the total loss, converter included, at my current?" The rule of thumb that comes out of the numbers: the higher the current, the more vertical delivery pays.

Deep dive: the numbers and details

This part holds the square-law arithmetic, the loss audit table, published converter results, the current sweep and the practical limits. Skip it if the overview is all you need.

Why the square law decides the layout

Two points explain it. The first is the voltage argument. Deliver 1 kW at 1 V and the current is 1,000 A. Deliver the same power at 48 V and it is about 20.8 A. Through an illustrative 1 mΩ path, the first case loses 1,000 W and the second about 0.43 W, a ratio of 48 squared, or 2,304. The University of Illinois Chicago (UIC) authors make the same point in their 2023 paper: PCB-level conversion means 48 times the current and 48 squared times the loss.

The second is a useful identity. Loss divided by delivered power is I²R divided by VI, which reduces to IR divided by V. University of Minnesota authors state this directly in a 2026 preprint: resistive loss as a fraction of delivered power equals the supply droop as a fraction of the rail voltage. A 2% droop is therefore a 2% loss, and you can read the efficiency cost straight off an IR drop budget.

The loss audit

Here is a comparison of three layouts feeding the same load. The load current and voltage are illustrative choices. The resistances are vendor claims from Vicor, which sells vertical modules: about 200 µΩ for a lateral path in a May 2024 article, about 70 µΩ for a close-coupled lateral layout and about 10 µΩ for a design that pushes most current through bottom-side modules. Vicor quoted those last two at about 800 A and at 1,200 A, and we apply them all at 1,000 A, assuming that resistance stays constant.

The converter efficiencies are also assumptions. For lateral we use 90%, the figure UIC assumes for its PCB-level reference. For vertical we use 88%, which Infineon showed at APEC 2025 for a 54 V to 0.7 V module at 300 A. That is a vendor claim at a different voltage and current from our model, so treat it as a placeholder. The regulator is assumed to raise its output so the load always sees 0.75 V.

At 1,000 A into 0.75 V (750 W)Lateral, long pathLateral, closeVertical
Path resistance (vendor claim)200 µΩ70 µΩ10 µΩ
I²R loss in the path200 W70 W10 W
Voltage drop200 mV (26.7% of 0.75 V)70 mV (9.3%)10 mV (1.3%)
Regulator output power950 W820 W760 W
Converter efficiency (assumed)90%90%88%
Input power at 48 V1,055.6 W911.1 W863.6 W
Conversion loss105.6 W91.1 W103.6 W
Total loss305.6 W161.1 W113.6 W
End-to-end efficiency71.1%82.3%86.8%

To check a column, take the vertical one. The loss is 1,000 squared times 10 µΩ, which is 10 W. Add 750 W of load and the regulator must supply 760 W. Dividing by 0.88 gives 863.6 W at the input, so the total loss is 863.6 minus 750, or 113.6 W. The 48 V side barely registers: at about 22 A or less, an illustrative 1 mΩ path loses under 0.5 W in every column, and we have left it out.

Now compare the vertical column with the close lateral one. I²R falls by 60 W, or about 86%. Conversion loss rises by about 12.5 W. The net saving is about 47.5 W, or about 29% of the total. Against the long lateral path, the saving is about 192 W, or about 63%. So the answer to "how much does vertical save?" depends mainly on which lateral design you are replacing.

The model also shows where the loss ends up. In the close lateral case, the path accounts for about 43% of the total. In the vertical case it is about 9%, and the converter takes the other 91%.

TDK's February 2026 Electronic Design article shows the same general shape, listing a 70% cut in I²R loss and a 13.6% cut in system power loss for vertical against standard lateral delivery. It gives no test conditions, so this is a vendor claim too.

What vertical converters achieve today

Because conversion decides the result, the efficiency you assume matters more than any other input. Here is what we could trace. Boundaries differ between the rows, so they should not be ranked against one another.

SourceDesignReported efficiencyStatus
UC Berkeley, APEC 2024Single-stage 48 V to 1 V, tested to 1,500 A92.7% peak at 395 A and 85.7% at 1,500 A, gate drive includedMeasured on a lab prototype
Infineon, APEC 2025 plenary54 V to 0.7 V module, GaN plus silicon88% at 0.7 V and 300 AVendor claim on a slide
UIC, 2026 preprint70 distributed regulators, 48 V to 1 V, 1 kW into a 500 mm² load84% end to end, using 54% of the area under the loadModeled, covers conversion and distribution

The Berkeley row shows why the operating point matters. Efficiency falls 7 points between peak and full load, and at 85.7% the converter sheds about 250 W of heat at 1,500 A (1,500 W divided by 0.857, minus 1,500 W). Swap that 85.7% into our model and the vertical total rises from 113.6 W to about 136.8 W. The saving against close lateral falls from about 29% to about 15%. Berkeley's conditions differ from ours, as its output is 1 V, so this is a sensitivity test and not a prediction.

The UIC work reaches a similar conclusion from another direction. Its 2023 paper finds that all the proposed architectures lose under 10% in the distribution network and over 10% in the converters, and it names converter efficiency as the thing to improve.

How the answer changes with current

Keep the same assumptions (70 µΩ at 90% against 10 µΩ at 88%, into 0.75 V) and vary the current. This is illustrative. Real resistance and efficiency both change with load and temperature, and our model holds them fixed. The last column gives the vertical converter efficiency at which the two totals become equal.

CurrentLateral I²RVertical I²RLateral totalVertical totalVertical savesBreak-even efficiency
300 A6.3 W0.9 W32.0 W31.7 W0.3 W (about 1%)87.9%
500 A17.5 W2.5 W61.1 W54.0 W7.1 W (about 12%)86.6%
1,000 A70 W10 W161.1 W113.6 W47.5 W (about 29%)83.4%
2,000 A280 W40 W477.8 W250.0 W227.8 W (about 48%)77.9%

The break-even column works as a quick decision tool. At 1,000 A, for instance, a vertical converter below about 83.4% would lose more than a good 90% lateral design with 70 µΩ. Against a 200 µΩ lateral path, the threshold falls to 72%, so the baseline chosen changes the answer a great deal.

Vertical delivery does not end the square law either. A Google Research paper in IEEE T-CPMT (2026) describes accelerator current demand approaching and exceeding 10,000 A, according to its abstract. At that current, the same illustrative 10 µΩ path would lose 1 kW and drop 100 mV, or 13.3% of a 0.75 V rail.

What a loss table leaves out

Heat lands in a new place. The loss that was once spread across a board now concentrates under the die. UIC's 1 kW substrate-embedded model puts junction temperature above 110 °C without thermal management, with loss rising to 225 W and efficiency falling to 81.6%. With micro-channel cooling at 1.6 g/s, it reports about 84 °C, 210 W and 82.6%. Berkeley's prototype, which has no heat sink, ran continuously at 1,300 A on air, and the authors say that going higher needs better heat sinking or liquid cooling.

Area is the hard limit. UIC's 2026 and 2023 studies both work to 2 A/mm², with 1 kA into a 500 mm² die as the reference load. Berkeley's prototype measures 202.5 by 25.8 mm, or about 5,225 mm². By our arithmetic, 1,500 A over that box footprint is about 0.29 A/mm². That is a fair result for a board-level prototype with a different aim, and it shows how much shrinking separates board-level hardware from a die-shadow target. UIC's higher-efficiency variants need nearly 75% of the load die area, and its authors raise concerns about fabrication reliability and thermal stress at that level.

Vias and bumps open up. This one helps vertical. In UIC's 2023 model, a PCB-level reference needs an unreasonably large 1,200 mm² die for its 1 kA, while a vertical approach can feed a 500 mm² die using about 1% of the BGAs and 2% of the C4 bumps. For related packaging context, see our post on advanced semiconductor packaging.

Transients need separate analysis. UIC's 2026 abstract gives a peak steady-state drop of 2.7% and a peak transient drop of 9% without decoupling capacitors. A DC audit will not show you that second number.

Mechanics count as well. The Google abstract lists thermal management, warpage and manufacturing as open challenges alongside power and signal integrity, and it treats input voltage and module granularity as design choices. Choose these with the package team from the start. Our chiplet and advanced packaging lifecycle on The Semiconductor Hub shows where interposer and substrate decisions fall in a program.

Running this audit on your own design

  1. Start from your real lateral design. Extract path resistance at temperature. Using someone else's 200 µΩ will overstate the gain if yours is 70 µΩ.
  2. Use your own current profile. A chip that spends most of its time at 400 A should be judged mainly at 400 A, even if its peak is much higher.
  3. Ask for efficiency at your operating point. Get it at your voltage, current and temperature, with gate drive included, and be clear about what the boundary covers.
  4. Calculate your break-even efficiency. Divide the vertical regulator's output power by the lateral design's input power. If the quoted module is below that number, keep the lateral layout or shorten its path.
  5. Check that the heat has somewhere to go. Rerun the loss table at the temperature your cooling can actually hold.

University of Minnesota authors offer a useful yardstick for the whole chain. If a first stage reaches 98%, the rest of the system must achieve 91.8% to meet a 90% end-to-end goal, and they treat 90% as a level that is within reach but needs several open problems solved. None of the figures traced in this post reaches 90% at full load, so the case for vertical today rests on high-current designs, where the copper loss is large enough to pay for the converter.

Sources

The worked calculations use illustrative load figures and assumed converter efficiencies, and they hold resistance and efficiency constant. Vendor figures are the companies' own claims, and preprint results are modeled unless stated otherwise.